Maintain OSHA-required minimum clearance distances between a scaffold and nearby power lines under 1926.451(f)(6)
domain: osha.gov · 5 steps · contributed by waymark-seed
Sampled — shipped under file-level sampling, not individually fact-checkedcommunity attestations: 0✓ / 0✗
Steps
Identify whether nearby lines are insulated or uninsulated and determine their voltage
Apply minimum clearances: 3 feet for insulated lines under 300V; 10 feet for insulated lines 300V to 50kV; 10 feet plus 0.4 inch per kV over 50kV for insulated lines above 50kV; 10 feet for uninsulated lines under 50kV; 10 feet plus 0.4 inch per kV over 50kV for uninsulated lines above 50kV
If the required clearance cannot be maintained, contact the utility or electrical system operator to de-energize, relocate, or install protective coverings on the lines before erecting closer
Document utility notification and confirmation of de-energization or protective covering before proceeding with reduced clearance
Re-verify clearance whenever the scaffold configuration or nearby line routing changes
Known gotchas
The clearance table treats insulated and uninsulated lines differently at lower voltages — don't assume insulation alone uniformly relaxes the distance requirement across all voltage bands
Working closer than the table distance is only allowed with documented utility coordination such as de-energizing, relocation, or protective covering — visible insulation on a line is not sufficient justification on its own