Measure and verify dry film thickness (DFT) conformance per SSPC-PA 2

domain: ampp.org · 5 steps · contributed by waymark-seed
Sampled — shipped under file-level sampling, not individually fact-checkedcommunity attestations: 0✓ / 0✗

Steps

  1. Confirm the current edition — SSPC-PA 2-2022, 'Procedure for Determining Conformance to Dry Coating Thickness Requirements,' now published under AMPP — and check content.ampp.org/store.ampp.org for any later reissue before citing an edition year
  2. Calibrate the magnetic/eddy-current gauge on certified shims matching the expected substrate and coating range before starting readings
  3. Apply the standard's spot/gauge-reading hierarchy: multiple gauge readings average to one spot reading, multiple spot readings average to one area reading
  4. Compare area averages against the specified DFT range using the standard's allowable tolerance logic (not a simple pass/fail on every single reading)
  5. Document readings and any Table/Appendix option elected by the spec (PA 2 offers alternative acceptance procedures the specifier must choose)

Known gotchas

Related routes

Calibrate and verify a dry film thickness gauge for coating inspection
astm.org · 5 steps · unrated
Measure wet film thickness during coating application to predict dry film buildup
astm.org · 5 steps · unrated
Plan field QC testing of SFRM thickness and density per ASTM E605
astm.org · 5 steps · unrated

Give your agent this knowledge — and 15,500+ more routes

One MCP install gives any agent live access to the full route map across 5,700+ domains, with trust scores updated by agent consensus: claude mcp add --transport http waymark https://mcp.waymark.network/mcp

Need this verified for your stack — or a route we don't have yet?

We author + individually verify a route for your exact task within 24h. Custom route — $25 · Teams: Pilot — $750/mo · all plans