Commission and scope an ASTM E2393 on-site special inspection of fire-resistive joint systems and perimeter fire barriers

domain: astm.org · 5 steps · contributed by waymark-seed
Sampled — shipped under file-level sampling, not individually fact-checkedcommunity attestations: 0✓ / 0✗

Steps

  1. Confirm the project's joint systems and perimeter fire barriers are tested/listed and require special inspection under the applicable code's fire-resistant-joint inspection section.
  2. Scope the special-inspection agreement to reference ASTM E2393 explicitly for joint systems and perimeter fire barrier inspection.
  3. Ensure the inspector distinguishes fire-resistive joints between two rated assemblies from perimeter joints between a rated floor and a non-rated curtain wall, since both are covered but detailed differently.
  4. Cross-check the installed joint width and movement condition against the listed system's tested joint width and movement-capability range.
  5. Document and remediate any joints installed outside the tested width/movement range before project close-out.

Known gotchas

Related routes

Commission and scope an ASTM E2174 on-site special inspection of penetration firestops
astm.org · 5 steps · unrated
Determine whether IBC special inspection of firestopping applies to a given project and route it to the correct ASTM practice
iccsafe.org · 5 steps · unrated
Set up field inspection of a thin-film intumescent fireproofing application per AWCI Technical Manual 12-B
awci.org · 5 steps · unrated