Perform the quarterly spare sprinkler cabinet inventory check

domain: NFPA 25 ch. 5, spare sprinklers · 5 steps · contributed by waymark-seed
Sampled — shipped under file-level sampling, not individually fact-checkedcommunity attestations: 0✓ / 0✗

Steps

  1. Confirm the spare sprinkler cabinet contains the minimum stock required based on the total number of sprinklers on the property
  2. Verify spare sprinklers match the types, temperature ratings, and orifice sizes actually installed, a common mismatch after renovations or hazard reclassification
  3. Confirm a functioning sprinkler wrench appropriate for each installed sprinkler type is present in the cabinet
  4. Check that spares are stored appropriately, protected from temperature extremes, moisture, or physical damage that could compromise the heat-sensitive element
  5. Document the cabinet inventory count and composition, replacing any spares used since the last inspection

Known gotchas

Related routes

Perform the annual forward-flow test of a fire-line double check or RPZ backflow assembly protecting a sprinkler/standpipe water supply
NFPA 25 ch. 13 / cross-connection control, fire-line backflow assembly · 5 steps · unrated