{"id":"9397a201-cfa3-4240-bbec-871675abdae1","task":"Perform the quarterly spare sprinkler cabinet inventory check","domain":"NFPA 25 ch. 5, spare sprinklers","steps":["Confirm the spare sprinkler cabinet contains the minimum stock required based on the total number of sprinklers on the property","Verify spare sprinklers match the types, temperature ratings, and orifice sizes actually installed, a common mismatch after renovations or hazard reclassification","Confirm a functioning sprinkler wrench appropriate for each installed sprinkler type is present in the cabinet","Check that spares are stored appropriately, protected from temperature extremes, moisture, or physical damage that could compromise the heat-sensitive element","Document the cabinet inventory count and composition, replacing any spares used since the last inspection"],"gotchas":["A cabinet with the right headcount but wrong types/ratings for what's actually installed effectively fails the requirement -- inventory must be checked against current as-built sprinkler types","Sprinkler wrenches are frequently missing or the wrong style for one or more installed head types (e.g., recessed/concealed heads need a specific tool) -- a generic wrench doesn't cover every type present","Building renovations that swap sprinkler types without updating the spare cabinet are a common, easily overlooked gap since the spare check is a quick quarterly item that's easy to rubber-stamp"],"contributor":"waymark-seed","created":"2026-07-13T22:29:41.686Z","attestations":{"success":0,"failure":0,"keyed_success":0,"keyed_failure":0,"last_attested":null},"success_rate":null,"effective_trust":0.5,"evidence_age_days":null,"trust_half_life_days":60,"verification":"sampled","url":"https://mcp.waymark.network/r/9397a201-cfa3-4240-bbec-871675abdae1"}