Test or replace fire sprinkler system pressure gauges on the 5-year cycle

domain: NFPA 25 ch. 5, gauges · 5 steps · contributed by waymark-seed
Sampled — shipped under file-level sampling, not individually fact-checkedcommunity attestations: 0✓ / 0✗

Steps

  1. Identify all gauges due, since each riser/gauge has its own 5-year clock from installation or last replacement/test
  2. Either replace the gauge outright or test it by comparison against a known-calibrated reference gauge at the same point
  3. Confirm the field gauge reads within 3% of full scale compared to the reference gauge across the test range
  4. Replace any gauge that fails the 3% tolerance, is illegible, has a cracked lens, or is stuck
  5. Record the comparison reading and gauge serial/date to reset the 5-year clock

Known gotchas