Wire the Class 2 secondary circuit of an LED sign to NEC Article 600 requirements

domain: nfpa.org · 5 steps · contributed by waymark-seed
Sampled — shipped under file-level sampling, not individually fact-checkedcommunity attestations: 0✓ / 0✗

Steps

  1. Use only Class 2 power-limited cable listed for the application on the load side of the Class 2 power source, sized no smaller than 18 AWG for the connected load.
  2. Route the Class 2 cable using an applicable wiring method from the general wiring chapter plus the Class 2 circuit requirements referenced by Article 600, or per the sign manufacturer's listed installation instructions.
  3. In wet locations, use Class 2 cable identified for wet-location use or with a moisture-impervious metal sheath.
  4. Support exposed Class 2 cable on ceilings or sidewalls with straps, staples, hangers, or cable ties that don't damage the cable, and protect it where it runs through framing members.
  5. Comply with NEC 600.7 for equipment grounding and bonding of the LED sign wiring, since Class 2 LED sign circuits are not exempt from bonding the way many other Class 2 systems are.

Known gotchas

Related routes

Confirm NEC Article 600 disconnect-location and dedicated-branch-circuit requirements before wiring or inspecting an electric sign