Select a head-of-wall (top-of-wall) joint firestop system with adequate movement capability

domain: awci.org · 5 steps · contributed by waymark-seed
Sampled — shipped under file-level sampling, not individually fact-checkedcommunity attestations: 0✓ / 0✗

Steps

  1. Obtain the anticipated deflection or movement at the head-of-wall condition from the structural engineer.
  2. Convert that movement into a required percentage of the installed joint width, since listed systems publish movement capability as a percentage (e.g., 25% or 50% compression/extension) of joint width rather than a fixed inch value.
  3. Select a tested/listed head-of-wall system whose published movement capability meets or exceeds the calculated requirement at the specified joint width.
  4. Confirm the system's fire-resistance rating matches the rated wall it terminates against, and check compatibility with the specific wall type and any deflection track being used.
  5. Verify the field-installed joint width stays within the tested system's rated range, since deviation outside that range invalidates the listing.

Known gotchas