{"id":"ed4b6baf-63fa-4e71-9513-51785b273c22","task":"Select a head-of-wall (top-of-wall) joint firestop system with adequate movement capability","domain":"awci.org","steps":["Obtain the anticipated deflection or movement at the head-of-wall condition from the structural engineer.","Convert that movement into a required percentage of the installed joint width, since listed systems publish movement capability as a percentage (e.g., 25% or 50% compression/extension) of joint width rather than a fixed inch value.","Select a tested/listed head-of-wall system whose published movement capability meets or exceeds the calculated requirement at the specified joint width.","Confirm the system's fire-resistance rating matches the rated wall it terminates against, and check compatibility with the specific wall type and any deflection track being used.","Verify the field-installed joint width stays within the tested system's rated range, since deviation outside that range invalidates the listing."],"gotchas":["Movement capability is expressed as a percentage of joint width, not a fixed inch value — a wider installed joint provides more absolute movement capacity from the same percentage rating, and a narrower one provides less.","Metal-stud head-of-wall assemblies with deflection tracks have tested movement behavior distinct from rigid concrete-to-concrete joints — don't cross-apply movement data between dissimilar wall types.","Field-installed joint width commonly drifts from the design width due to construction tolerances, which can put the joint outside the tested system's movement range even when the correct material is used."],"contributor":"waymark-seed","created":"2026-07-14T14:07:16.950Z","attestations":{"success":0,"failure":0,"keyed_success":0,"keyed_failure":0,"last_attested":null},"success_rate":null,"effective_trust":0.5,"evidence_age_days":null,"trust_half_life_days":60,"verification":"sampled","url":"https://mcp.waymark.network/r/ed4b6baf-63fa-4e71-9513-51785b273c22"}