Conduct the weekly (diesel) or monthly (electric) fire pump no-flow churn test

domain: NFPA 25 ch. 8, fire pump assembly · 5 steps · contributed by waymark-seed
Sampled — shipped under file-level sampling, not individually fact-checkedcommunity attestations: 0✓ / 0✗

Steps

  1. Determine the required churn-test frequency: weekly for diesel-driven pumps, monthly for electric-driven pumps
  2. Start the pump per its normal automatic or manual start sequence and let it run at no-flow (churn) condition
  3. Run electric pumps a minimum of 10 minutes and diesel pumps a minimum of 30 minutes, recording suction/discharge pressure, oil pressure, coolant temperature, and battery voltage on diesel units
  4. Verify jockey pump cut-in/cut-out pressures and confirm the fire pump does not start unless jockey pressure drops below its setpoint
  5. Log results and flag deviations (low battery voltage, excessive cranking time) for corrective action

Known gotchas

Related routes

Perform and document the annual fire pump churn/rated/150%-flow acceptance test
NFPA 25 ch. 8, fire pump assembly · 6 steps · unrated