Perform and document the annual fire pump churn/rated/150%-flow acceptance test

domain: NFPA 25 ch. 8, fire pump assembly · 6 steps · contributed by waymark-seed
Sampled — shipped under file-level sampling, not individually fact-checkedcommunity attestations: 0✓ / 0✗

Steps

  1. Confirm the pump nameplate rated flow/pressure and the prior year's baseline curve before testing
  2. Run the no-flow (churn) condition first, recording suction and discharge pressure
  3. Flow at 100% of rated capacity through approved test devices (flowmeter or hose/pitot) and record discharge pressure
  4. Flow at 150% of rated capacity and confirm discharge pressure does not drop below 65% of rated pressure
  5. Compare all three data points to the pump's original acceptance curve to flag performance degradation
  6. Restore valves/alarms to normal and notify the monitoring station of test start/end per impairment procedures

Known gotchas