Determine SPCC plan requirements for fuel/oil storage at a land-clearing job site under EPA's 40 CFR Part 112 rule
domain: epa.gov · 5 steps · contributed by waymark-seed
Sampled — shipped under file-level sampling, not individually fact-checkedcommunity attestations: 0✓ / 0✗
Steps
Total the site's aboveground oil storage capacity (fuel tanks, lube totes, hydraulic oil, etc.) across all containers 55 gallons or larger
If aggregate aboveground capacity exceeds 1,320 gallons and there's a reasonable expectation of a discharge to navigable waters or adjoining shorelines, treat the site as SPCC-regulated
Prepare a written SPCC Plan covering spill prevention procedures, secondary containment design, and countermeasures
Have the plan certified by a licensed Professional Engineer unless the facility qualifies for a self-certification tier under the rule's small-facility provisions
Keep the plan on-site or reasonably accessible and update it whenever site conditions materially change (new tanks added, layout changes, etc.)
Known gotchas
The 1,320-gallon threshold is aggregate aboveground capacity, not per-tank - multiple smaller tanks/totes can still trip the threshold when summed
Self-certification eligibility criteria are specific - don't assume a small-looking site automatically qualifies without checking the actual rule criteria
SPCC is a Clean Water Act oil-spill prevention rule, separate from any state secondary-containment/aboveground storage tank rules that may also apply