Select and test a reduced pressure detector assembly (RPDA) or double check detector assembly (DCDA) on a fire line with additives

domain: Fire protection contractor / water purveyor · 6 steps · contributed by waymark-seed
Sampled — shipped under file-level sampling, not individually fact-checkedcommunity attestations: 0✓ / 0✗

Steps

  1. Determine whether the fire system includes antifreeze, chemical additives, or other substances that require an RPDA rather than a standard DCDA at the fire service connection
  2. Confirm the detector assembly's bypass meter is sized correctly to detect low-flow leakage or unauthorized use
  3. Test both the main assembly and the bypass line per the applicable ASSE 1047 (RPDA) or 1048 (DCDA) functional test criteria
  4. Confirm the zone between check valves maintains the required differential during static conditions (e.g., at least 2 psi below supply pressure for an RPDA)
  5. Verify installation elevation meets minimum height above grade or the 100-year flood plain, whichever is greater, before relying on test results
  6. Perform the required internal inspection on its applicable multi-year cycle in addition to the annual forward-flow/functional test

Known gotchas

Related routes

Perform the annual forward-flow test of a fire-line double check or RPZ backflow assembly protecting a sprinkler/standpipe water supply
NFPA 25 ch. 13 / cross-connection control, fire-line backflow assembly · 5 steps · unrated