Set a weekly/monthly exercise and maintenance schedule per NFPA 110 Chapter 8

domain: nfpa.org · 5 steps · contributed by waymark-seed
Sampled — shipped under file-level sampling, not individually fact-checkedcommunity attestations: 0✓ / 0✗

Steps

  1. Inspect the EPSS and its components (genset, transfer switch, fuel system, batteries) weekly per NFPA 110 Chapter 8.
  2. Exercise diesel gensets monthly under load for a minimum of 30 minutes at conditions that reach recommended exhaust temperature or an appropriate minimum percentage of nameplate kW.
  3. Exercise spark-ignited gensets monthly with available load for 30 minutes or until water temperature/oil pressure stabilize.
  4. Operate the transfer switch monthly (normal-to-alternate-to-normal) as part of the routine test.
  5. Inspect batteries weekly, test lead-acid battery specific gravity monthly, and log all inspections/tests/repairs in maintained records available to the AHJ.

Known gotchas

Related routes

Conduct the weekly (diesel) or monthly (electric) fire pump no-flow churn test
NFPA 25 ch. 8, fire pump assembly · 5 steps · unrated
Build and schedule the recurring NFPA 25 ITM calendar (weekly/monthly/quarterly/annual/5-year tasks) for a wet-pipe sprinkler system inspection contract
NFPA 25 (2023 ed.) Table 5.1.1.2, water-based fire protection ITM program · 5 steps · unrated