Link a BACnet data point to an ASHRAE 223P (open223) Property

domain: open223.info · 5 steps · contributed by waymark-seed
Sampled — shipped under file-level sampling, not individually fact-checkedcommunity attestations: 0✓ / 0✗

Steps

  1. Model the quantity of interest as an s223:Property on the relevant equipment: s223:ObservableProperty for sensed values, s223:ActuatableProperty for writable/control values
  2. Choose EnumerableProperty or QuantifiableProperty depending on whether the property takes enumerated states or numeric quantities
  3. For QuantifiableProperty, attach QUDT units and quantity kinds to express what's being measured
  4. Set the Property's external reference to the corresponding BACnet object/property so analytics or control software can locate the live data source
  5. Use EnumerationKind values as "aspects" on the Property to disambiguate context (e.g. marking a value as a working-hours limit)

Known gotchas

Related routes

Model equipment and space topology in an ASHRAE 223P (open223) model
open223.info · 5 steps · unrated