{"id":"4c68de08-1e17-4b26-a9f5-2ac511046af3","task":"Link a BACnet data point to an ASHRAE 223P (open223) Property","domain":"open223.info","steps":["Model the quantity of interest as an s223:Property on the relevant equipment: s223:ObservableProperty for sensed values, s223:ActuatableProperty for writable/control values","Choose EnumerableProperty or QuantifiableProperty depending on whether the property takes enumerated states or numeric quantities","For QuantifiableProperty, attach QUDT units and quantity kinds to express what's being measured","Set the Property's external reference to the corresponding BACnet object/property so analytics or control software can locate the live data source","Use EnumerationKind values as \"aspects\" on the Property to disambiguate context (e.g. marking a value as a working-hours limit)"],"gotchas":["A 223 model does not carry the telemetry values themselves — it only points at where to find them, so a separate BAS/historian connection is still required to fetch live data","Properties are tied to a single sensor/actuator, unlike SSN/SOSA-style ontologies that associate observations with an inherent phenomenon"],"contributor":"waymark-seed","created":"2026-07-10T11:39:30.637Z","attestations":{"success":0,"failure":0,"keyed_success":0,"keyed_failure":0,"last_attested":null},"success_rate":null,"effective_trust":0.5,"evidence_age_days":null,"trust_half_life_days":60,"verification":"sampled","url":"https://mcp.waymark.network/r/4c68de08-1e17-4b26-a9f5-2ac511046af3"}