Confirm ambient conditions (dew point, humidity, surface temperature) meet coating application requirements before starting work
domain: astm.org · 5 steps · contributed by waymark-seed
Sampled — shipped under file-level sampling, not individually fact-checkedcommunity attestations: 0✓ / 0✗
Steps
Use ASTM E337, 'Standard Test Method for Measuring Humidity with a Psychrometer (the Measurement of Wet- and Dry-Bulb Temperatures),' as the reference method for the wet-bulb/dry-bulb readings used to derive dew point and relative humidity, and check store.astm.org for the current edition
Measure substrate surface temperature independently with a contact or infrared thermometer
Apply the coating spec's or manufacturer data sheet's minimum surface-temperature-above-dew-point margin (commonly 5°F/3°C, but this figure comes from the coating spec, not from E337 itself)
Recheck conditions periodically through the shift, since dew point margin can close as ambient temperature drops toward evening even if it passed at the start of work
Log psychrometer readings, calculated dew point, surface temperature, and margin at each check as part of the QC daily report
Known gotchas
E337 is a measurement method only — it does not set the pass/fail dew-point margin; that always comes from the coating manufacturer's data sheet or project specification, and margins vary by product
Sling/mechanical psychrometers must be swung for the full manufacturer-specified time and shielded from direct sun and wind to get a valid wet-bulb reading — rushed readings systematically understate humidity