Decide what to do when concrete moisture test results (F2170/F1869) exceed the flooring manufacturer's threshold
domain: astm.org · 5 steps · contributed by waymark-seed
Sampled — shipped under file-level sampling, not individually fact-checkedcommunity attestations: 0✓ / 0✗
Steps
Compare results against the specific flooring or coating manufacturer's published acceptance threshold — this is a product-specific number, not a single industry-wide cutoff.
If only slightly over threshold, evaluate a documented dry-out period with re-testing before considering mitigation, since additional slab drying is often the lowest-cost path.
If dry-out isn't practical on schedule, evaluate a moisture-mitigation system that the flooring manufacturer has approved in writing as compatible with the specific flooring product being installed.
Consider substituting a more moisture-tolerant flooring system (e.g., certain urethane cement/cementitious urethane systems tolerate higher RH/MVER than thin epoxy coatings) if mitigation isn't cost-effective.
Get the flooring manufacturer's written sign-off on whichever path is chosen — warranty coverage typically depends on following their documented moisture protocol exactly.
Known gotchas
Never average or convert between F1869 and F2170 numbers — they measure different things and are not directly comparable or interchangeable.
A flooring failure from unaddressed moisture is rarely covered by manufacturer warranty — get written mitigation or acceptance sign-off before proceeding, not just a verbal okay.