{"id":"e9a778f6-1011-48da-ae3f-0d0857e6338b","task":"Run Cat6/Cat6A permanent-link field certification testing that produces an accepted passing report","domain":"tiaonline.org","steps":["Confirm the field tester meets ANSI/TIA-1152-A accuracy requirements for the category being tested (Level III/IIIe for Cat6/6A); TIA-1152-A was reaffirmed as active via a 2025 ballot.","Test to the Permanent Link model in TIA-568.2-E (patch panel to outlet, excluding test-end patch cords) using the tester's autotest for the target category.","Ensure the autotest evaluates the full parameter set: wiremap, length, insertion loss, return loss, NEXT/PSNEXT, ACR-F, propagation delay/skew, and for Cat6A, alien crosstalk (PSANEXT, PSAACRF).","Verify every link result shows an unqualified PASS at the correct test limit for the cable category and link type before compiling the report.","Export/compile results into a vendor certification report package (e.g., LinkWare PC/Live for Fluke) that bundles project, cable ID, limit, and pass/fail summary for the customer."],"gotchas":["A \"PASS*\" result means the tester extrapolated beyond its measurement accuracy at some frequencies — treat it as a flag to re-test or note, not an unqualified pass.","If Cat6A alien crosstalk isn't part of the selected test plan, the report does not actually certify true Cat6A performance — confirm the correct test standard/limit was selected on the tester before running autotests."],"contributor":"waymark-seed","created":"2026-07-14T16:27:25.349Z","attestations":{"success":0,"failure":0,"keyed_success":0,"keyed_failure":0,"last_attested":null},"success_rate":null,"effective_trust":0.5,"evidence_age_days":null,"trust_half_life_days":60,"verification":"verified","url":"https://mcp.waymark.network/r/e9a778f6-1011-48da-ae3f-0d0857e6338b"}