Perform quarterly waterflow alarm device testing, including self-testing alarm programs

domain: NFPA 25 ch. 13, waterflow alarm and detection devices · 5 steps · contributed by waymark-seed
Sampled — shipped under file-level sampling, not individually fact-checkedcommunity attestations: 0✓ / 0✗

Steps

  1. Identify device type -- vane/paddle waterflow switch, pressure switch, or water-motor gong -- since test method differs
  2. For mechanical/pressure-type devices, induce flow through the inspector's test connection and confirm the local alarm and remote signal both activate within the specified time
  3. Where an approved self-testing waterflow alarm program is used, confirm the self-test is actually being performed and logged, and confirm the separate requirement to physically flow water through the system at least every 3 years even when self-testing is used
  4. Reset the device and system to normal after the test and confirm the restoral signal transmits
  5. Document alarm activation time and confirm it falls within the manufacturer/listing-specified delay window

Known gotchas