Steps
Determine the installation's expected minimum ambient temperature and continuous-use protection needs
Select Class I (heated, maintains 40°F down to -30°F ambient) for climates with hard freezes and continuous protection requirements
Select Class II (insulated, frost-protected only) only where temperatures will not fall below 33°F
Avoid Class III (no freeze protection) wherever any freeze risk exists
Confirm the enclosure's drainage system limits internal water rise to the ASSE 1060 maximum (8 inches) and routes discharge away from the assembly
Verify heater components (for Class I) are rated for wet/damp environments and that test cocks/controls remain within 24 inches of the access point
Known gotchas
Class II frost protection is often mistakenly treated as adequate freeze protection — it is not rated for hard-freeze climates and will not reliably prevent assembly damage below 33°F
Enclosure lock mechanisms must pass a 20-pound deadweight drop test under ASSE 1060 — non-conforming aftermarket locks can void the enclosure's listing
Poor internal drainage design causing water to pool inside the enclosure can itself cause freeze damage, even in a nominally Class I heated unit, if the heater ever fails