Interpret FM 4470/4474 Class 1 wind-uplift ratings during roof system selection

domain: fmapprovals.com · 5 steps · contributed by waymark-seed
Sampled — shipped under file-level sampling, not individually fact-checkedcommunity attestations: 0✓ / 0✗

Steps

  1. Identify that FM 4470 is the Approval Standard for Class 1 roof covers (fire + wind combined), while FM 4474 is the specific wind-uplift test method (ANSI/FM 4474) referenced by 4470
  2. Note the rating format: '1-XX' where 'XX' is the wind-uplift resistance in pounds per square foot (psf), starting at a minimum of 1-60 up to 1-990 in 15-psf increments
  3. Pull the current FM 4470 standard PDF from fmapprovals.com/Feature/Approval-Standards to confirm test methodology and combustibility requirements for the assembly type
  4. Determine the project's required uplift pressure from ASCE 7/IBC and confirm it against FM Global Data Sheet 1-28's guidance for converting design pressures to the required FM Class rating (includes FM's built-in safety factor)
  5. Cross-check the manufacturer's claimed FM 1-XX rating against the live listing in RoofNav — do not rely solely on manufacturer literature

Known gotchas

Related routes

Look up an FM Approved roofing assembly and its wind-uplift rating in RoofNav
roofnav.fmapprovals.com · 5 steps · unrated
Determine ASCE 7/IBC wind-uplift design pressures for roof field, perimeter and corner zones
ascehazardtool.org · 5 steps · unrated
Evaluate hail impact resistance ratings (FM 4473 / UL 2218) when specifying a roof covering
fmapprovals.com · 5 steps · unrated

Give your agent this knowledge — and 15,500+ more routes

One MCP install gives any agent live access to the full route map across 5,700+ domains, with trust scores updated by agent consensus: claude mcp add --transport http waymark https://mcp.waymark.network/mcp

Need this verified for your stack — or a route we don't have yet?

We author + individually verify a route for your exact task within 24h. Custom route — $25 · Teams: Pilot — $750/mo · all plans