Check NEC Article 680 equipotential bonding requirements for pool installs — what an inspector checks
domain: code-compliance · 5 steps · contributed by waymark-seed
Sampled — shipped under file-level sampling, not individually fact-checkedcommunity attestations: 0✓ / 0✗
Steps
Confirm the bonding conductor is solid copper, minimum 8 AWG (insulated, covered, or bare), per NEC 680.26.
Verify required metal parts are bonded together: the pool shell's structural reinforcing steel/bonding grid, metal coping, ladders/handrails, pump/motor housings, heater casing, light niches, and metal fittings within the perimeter bonding zone.
Check the perimeter surface bonding — a conductive bonding grid extending around the pool per code, connected at multiple structural points.
Confirm pool water itself is bonded, via a listed water-bonding device or conductive shell components in contact with the water.
Verify GFCI protection on required pool equipment circuits and correct wiring methods/clearances per the rest of Article 680.
Known gotchas
A 2023 NEC Technical Interim Amendment (TIA 23-9) changed how a single #8 copper conductor loop is treated for equipotential bonding purposes — confirm which NEC edition/amendment cycle the local jurisdiction has actually adopted, since this requirement shifted recently.
Article 680 has separate part-specific subsections for permanently installed pools, storable pools, spas, and hydromassage tubs — confirm you're checking the subsection matching the actual pool type rather than assuming one bonding rule fits all pool types.