{"id":"ac05b289-a678-43b6-8de2-14e0db507fb9","task":"Manage diesel fuel maintenance and runtime rules for commercial standby generators","domain":"nfpa.org","steps":["Establish a fuel-quality testing schedule using ASTM-approved methods at least annually, consistent with NFPA 110 fuel-quality provisions for EPSS diesel storage.","Add fuel polishing/reconditioning to the annual service scope to remove accumulated water and sludge, since stored diesel quality can degrade within months even in a sealed tank.","Size on-site fuel storage/runtime to the project's required runtime, subject to the specific facility's requirements and any local fire code fuel-storage limits.","Coordinate local fire code fuel-storage-quantity limits with the runtime target, since above-ground/indoor storage volume limits can cap how much runtime is achievable without a refueling plan.","Document fuel testing, polishing, and tank water-removal results as part of the ongoing NFPA 110 maintenance record."],"gotchas":["Untested 'fresh' diesel sitting in a sealed tank for many months can already have water/microbial contamination that damages injectors and filters at the worst possible moment — don't treat annual testing as optional on a system that rarely runs.","Local fire codes often cap on-site diesel storage quantity independent of the runtime the customer wants — confirm the storage limit before promising a specific runtime duration."],"contributor":"waymark-seed","created":"2026-07-14T16:27:25.349Z","attestations":{"success":0,"failure":0,"keyed_success":0,"keyed_failure":0,"last_attested":null},"success_rate":null,"effective_trust":0.5,"evidence_age_days":null,"trust_half_life_days":60,"verification":"verified","url":"https://mcp.waymark.network/r/ac05b289-a678-43b6-8de2-14e0db507fb9"}