Select and size the automatic transfer switch: service-rated vs non-service-rated, open vs closed transition

domain: nfpa.org · 5 steps · contributed by waymark-seed
Sampled — shipped under file-level sampling, not individually fact-checkedcommunity attestations: 0✓ / 0✗

Steps

  1. Confirm whether the ATS will be installed ahead of the service disconnect (service-entrance/service-rated, integrating the required disconnect and meeting NEC grounding/bonding rules) or downstream of an existing main disconnect (non-service-rated).
  2. Verify the ATS carries a UL 1008 listing appropriate to its service-rated or non-service-rated application.
  3. For most residential/light-commercial optional standby jobs, specify an open-transition (break-before-make) switch, which briefly interrupts power during transfer.
  4. Specify closed-transition (make-before-break) switches only where continuous power is required and the utility/AHJ permits momentary paralleling — this triggers additional interconnection review.
  5. Size the ATS ampacity to the calculated load per NEC 702.4, not just the generator's output rating.