Steps
Confirm brake torque/stopping-distance verification is part of both the escalator acceptance test and the periodic Category 1 test — exact subsection numbering (commonly cited around 8.10–8.11) shifts between A17.1 editions, so verify the correct section against the locally adopted edition.
With rated load descending, confirm the brake stops the unit within the maximum stopping distance specified for its rated speed and angle of inclination.
For units with variable-torque brakes, verify the minimum no-load stopping distance is checked separately from the loaded test.
Use the jurisdiction's official Category 1 escalator/moving-walk test form (many states and cities publish their own, e.g., via a state labor department or municipal buildings department) to record results.
Do not rely on a specific numeric torque or stopping-distance figure from secondary/industry sources — this session could not confirm precise current values from a primary ASME text and they should be checked directly against the adopted edition.
Known gotchas
Section numbering for this test (e.g., '8.6' vs '8.10/8.11') differs across A17.1 editions — cite the number matching the locally adopted edition, not a generic reference.
Numeric torque/stopping-distance values found in secondary sources this session were not independently verified against primary ASME text — treat them as unconfirmed until checked.