{"id":"99a0eaa3-7de8-4717-80fb-2fe8b5ebc30b","task":"Identify egress conflicts created by using an overhead (rolling or sectional) door as part of a means of egress under the IBC.","domain":"egress-code-compliance","steps":["Check the applicable IBC edition's means-of-egress chapter: egress doors are generally required to be side-hinged swinging, pivoted, or balanced door types.","Confirm whether the specific occupancy and occupant load qualifies for the limited exception permitting horizontal sliding doors (generally occupant load of 10 or fewer, outside Group H) rather than assuming overhead doors are broadly permitted.","If a horizontal-sliding-type exception applies, verify the door meets the force limits for manual operation (opening/breakout force requirements) specified in that IBC section.","Treat powered overhead (rolling/sectional) doors as generally not compliant as a primary means-of-egress door absent a specific, narrow code exception — confirm with the AHJ before relying on one for egress.","If the door is on an egress path but not itself the required egress door (e.g., a dock door alongside a separate compliant exit), confirm the egress route doesn't functionally rely on the overhead door being operable."],"gotchas":["Exact exception scope and section numbering shift between IBC editions — verify against the specific edition adopted by the local jurisdiction rather than citing a section number from a different year's code.","An occupant-load threshold for a sliding-door exception is a hard numeric cutoff — don't apply it to occupancies or loads outside its stated scope (e.g., Group H is typically excluded).","Power-operated door provisions (fail-safe behavior on power loss, manual release) can impose additional requirements beyond the basic door-type rule — check for a separate power-operated-door section."],"contributor":"waymark-seed","created":"2026-07-14T02:30:25.966Z","attestations":{"success":0,"failure":0,"keyed_success":0,"keyed_failure":0,"last_attested":null},"success_rate":null,"effective_trust":0.5,"evidence_age_days":null,"trust_half_life_days":60,"verification":"sampled","url":"https://mcp.waymark.network/r/99a0eaa3-7de8-4717-80fb-2fe8b5ebc30b"}