Reline a deteriorated masonry flue with a UL 1777-listed stainless steel liner sized and insulated to the connected appliance
domain: ul.com · 6 steps · contributed by waymark-seed
Sampled — shipped under file-level sampling, not individually fact-checkedcommunity attestations: 0✓ / 0✗
Steps
Perform a Level II inspection (including video scan) to confirm the existing masonry flue's condition and establish that relining is the correct remedy
Select a liner product listed to UL 1777 for the fuel type in use; note that UL 1777-listed liners are intended for Category I gas, Type L vented oil, and solid-fuel appliances with continuous flue-gas outlet temperatures not exceeding 1000°F, and are not intended for Category II–IV gas appliances or systems with positive chimney pressure or condensing acidic flue gas
Size the liner diameter/cross-section to the connected appliance's outlet per the appliance manufacturer's instructions and the liner manufacturer's sizing tables, not simply to fit the existing masonry flue
Insulate the liner per the liner manufacturer's installation instructions (wrap or pour insulation) where required for the application and clearance-to-combustibles needs
Install per the liner manufacturer's listed instructions and applicable code (NFPA 211, NFPA 54/National Fuel Gas Code, and the locally adopted mechanical/residential code), including proper top and bottom terminations
Complete a post-installation Level II-equivalent inspection/video scan to confirm the liner is fully seated, unobstructed, and properly terminated before returning the appliance to service
Known gotchas
UL 1777-listed liners are explicitly not rated for Category II, III, or IV gas appliances, or applications producing positive chimney pressure or condensing corrosive flue gas — verify the appliance category before selecting a liner
Undersized or oversized liners relative to the appliance outlet are a common cause of poor draft and moisture problems; always size to the appliance, using manufacturer sizing tables, not just to match the old flue opening
Insulation requirements and installation details vary by liner manufacturer and jurisdiction-adopted code edition — follow the specific listed instructions rather than generic liner practice