Decide between AAMA/FGIA 501.2 and 501.3 for an installed curtain wall field water-leak investigation
domain: fgiaonline.org · 5 steps · contributed by waymark-seed
Sampled — shipped under file-level sampling, not individually fact-checkedcommunity attestations: 0✓ / 0✗
Steps
Confirm current scope of AAMA 501.3 on the FGIA store before citing it — publicly available summaries describe it as a field check of water penetration through installed exterior windows, curtain walls and doors by uniform air pressure difference; verify this wording against the current published scope.
Compare 501.3's chamber/uniform-air-pressure method (closer to a scaled-down field version of ASTM E1105) against 501.2's simpler hose-nozzle diagnostic spray.
Select 501.3 when a quantifiable pass/fail result under a defined pressure differential is needed (e.g., forensic/litigation-grade documentation); select 501.2 for quick diagnostic leak-location work.
Confirm equipment and crew availability — 501.3 requires a sealed test chamber against the wall, which is more setup-intensive than 501.2's hose rig.
Coordinate access (swing stage, lift) and building occupant notification separately for each method, since chamber setup for 501.3 typically takes longer per test location.
Known gotchas
Don't assume 501.2 and 501.3 are interchangeable — they differ in rigor and are used for different purposes (quick diagnostic vs. documented pressure-differential test).
Verify the current title and number for 501.3 directly on the FGIA store; older secondary sources may describe a superseded scope.