Run a compliant impairment (system-out-of-service) process for planned sprinkler work

domain: NFPA 25 ch. 15, impairment program · 6 steps · contributed by waymark-seed
Sampled — shipped under file-level sampling, not individually fact-checkedcommunity attestations: 0✓ / 0✗

Steps

  1. Assign/confirm the designated impairment coordinator responsible for the property's water-based fire protection impairment program
  2. Before taking the system out of service, verify the extent and expected duration of the impairment and inspect the affected areas to assess increased risk (fire watch needs)
  3. Notify all required parties before impairment begins: fire department, alarm monitoring company, insurance carrier, and other applicable AHJs
  4. Post an impairment tag at the system control valve, the fire department connection, and any other AHJ-required locations
  5. Upon completion, verify required inspections/tests confirm the system is fully operational before removing the tag, then notify the same parties that protection is restored
  6. Log the full impairment event (start, cause, duration, notifications, restoration verification) in the property's fire protection records