Identify which NFPA 701 test method applies: Test Method 1 (small-scale) for lighter single-layer fabrics ≤700 g/m² (21 oz/yd²), or Test Method 2 (large-scale) for heavier fabrics like most awning and tent materials above that weight
Request the fabric manufacturer's NFPA 701 test certificate/report showing which method was used and the pass criteria met
Confirm reported results meet pass thresholds: average mass loss ≤40%, no flaming drips burning longer than ~2 seconds average, and average afterflame ≤2 seconds after ignition source removal
Check whether the local jurisdiction or venue (event tents, public assembly canopies) requires the physical NFPA 701 certificate on-site, since fire marshals often ask for it at inspection
Keep a copy of the test report with the project's permit/fire-inspection file, not just a manufacturer web claim of NFPA 701 compliance
Known gotchas
A fabric can be tested under the wrong method for its actual weight/use; the two test methods aren't interchangeable, so verify the correct method was applied
"Flame-retardant" marketing claims are not the same as a documented NFPA 701 pass; always ask for the actual test report/certificate