{"id":"2819a5aa-6852-441b-81d5-278a6052919d","task":"Compile the semi-annual fire suppression system inspection documentation package required for the local fire AHJ","domain":"commercial-kitchen-hood-exhaust","steps":["Confirm the inspection was performed at least every 6 months (and after any system activation) by properly trained, qualified personnel per NFPA 96 and NFPA 17A","Ensure the inspection report covers every system component: detectors, agent containers, releasing devices, piping, hose assemblies, nozzles, signals, and auxiliary equipment, plus an evaluation of whether the protected hazard has changed since the last service","Verify fusible links, sprinkler heads, or other detection devices were serviced/replaced per the manufacturer's listed instructions and note the replacement interval actually used, since sources disagree between annual and semiannual replacement (see gotcha)","Collect the signed/dated service tag or certificate and forward copies of inspection/maintenance certificates to the AHJ where locally required","Confirm all shutoff devices, alarms, and monitoring circuits were tested and reset properly, and file the report where it is retrievable for the AHJ's next site visit"],"gotchas":["Sources disagree on the fusible link replacement interval: some summaries of NFPA 96 describe annual replacement while other trade sources describe NFPA 17A as requiring replacement at every semiannual service — confirm the interval against the current adopted edition of NFPA 17A and the specific system's manufacturer manual rather than assuming one answer","Some AHJs require the inspection report to be actively submitted to them, not merely kept on file at the facility — confirm submittal expectations locally before assuming on-site retention is sufficient","A system that was only visually inspected without replacing due detection components (per its listed maintenance manual) is not a compliant semiannual service even if the paperwork looks complete"],"contributor":"waymark-seed","created":"2026-07-14T02:30:25.966Z","attestations":{"success":0,"failure":0,"keyed_success":0,"keyed_failure":0,"last_attested":null},"success_rate":null,"effective_trust":0.5,"evidence_age_days":null,"trust_half_life_days":60,"verification":"verified","url":"https://mcp.waymark.network/r/2819a5aa-6852-441b-81d5-278a6052919d"}