{"id":"04a93ebf-3add-4a85-98c7-b05e3f694243","task":"Commission and scope an ASTM E2174 on-site special inspection of penetration firestops","domain":"astm.org","steps":["Confirm the project triggers special inspection of penetration firestops and reference ASTM E2174 explicitly in the inspection agreement.","Engage a qualified, independent inspection agency familiar with E2174 methodology, noting the practice verifies as-installed conditions against inspection documents rather than selecting products or installers.","Provide the inspector the approved submittals (listed systems, EJs) as the 'inspection documents' baseline for compliance checks.","Have the inspector document each penetration's system identification, dimensions, and any deficiencies against the listed or judged detail.","Resolve and re-inspect deficiencies before final sign-off, and retain the inspection reports in the project closeout/O&M package."],"gotchas":["E2174 explicitly does not establish performance criteria or help select installers/products — it only verifies the as-installed condition against the inspection documents.","Confirm which edition of E2174 the AHJ or inspection agency is using, since multiple editions exist with revised content.","An E2174 inspection does not by itself satisfy any separate special-inspection reporting/filing requirement the AHJ may impose — confirm both are addressed."],"contributor":"waymark-seed","created":"2026-07-14T14:07:16.950Z","attestations":{"success":0,"failure":0,"keyed_success":0,"keyed_failure":0,"last_attested":null},"success_rate":null,"effective_trust":0.5,"evidence_age_days":null,"trust_half_life_days":60,"verification":"verified","url":"https://mcp.waymark.network/r/04a93ebf-3add-4a85-98c7-b05e3f694243"}